:: home > network power analyzers > MAR-715
MAR-715 - TECHNICAL SPECIFICATIONS

Voltage measurement (true  R.M.S.)
Line-to-neutral 20...500 V~
Line-to-line 20...866 V~

Consumption
8 VA
 

Measuring range / Ammeter clamp in use
20...2000 A~ (scale 2000 A) / CP-2000-200
2...200 A~ (scale 200 A) / CP-2000-200
10...1000 A~ / CPR-1000
5...500 A~ / CPR-500
2...200 A~ / CP-200
1...100 A~/ CP-100
50 mA  to  5 A~  / CP-5
5A...20 kA~/ C-Flex
Crest  factor: 1,75

Frequency
45...65 Hz

Power supply voltage
230 V~

Voltage tolerance
± 15 %

Internal power supply
Batery: 12 V

Operation autonomy with battery
Max.: 8 h

Analyzer functions
Program: energy
Optional: harmonics, flicker, disturbances, check meter and fast check

Basic measurable parameters
Voltage, current, active power, reactive power, energy, V and A harmonics, flicker, disturbances and quality of the distribution system, real-time clock, average, max. and min. values of all parameters.

Accuracy (5 °C to 45 °C)
Voltage: 0,5 % of scale
Current: 0,5 % of scale
Powers: 1 % of scale
(Error due to ammeter clamps, not included)

Display
Graphic 160x160 pixels / Auto-OFF for inner battery saving

Record and data retrieval from PC
Data storage capacity: 1 Mbyte
Reacording period: Programmable
5 s ... 4 h (harmonics)
1 s ... 4 h (energy)
Optional trigger conditions by limit values
 

Software for PC
Power-VISUAL

Environmental conditions
Limit temperatures: 0 °C / ± 50 °C
Relative humidity: Max. 85 % no condensation

Standards
EN 61010 cat. III (Safety), IEC 60664, VDE 0110, UL 94, EN 60801, EN 50081-1, EN 50082-1, EN 61000-4-15.

Accessories
Cables, Power supply set, Software Power-Vision and RS-232 interface

Ammeters clamps avaiable
CP-2000/200 Clamp 2000/200A
CPR-1000 Clamp 1000A
CPR-500 Clamp 500A
CP-100 (M1-u) Clamp 100A
CP-5 Clamp 5A
CP-FLEX2000/200-45. single-phase (Length 45cm)
CP-FLEX 2000/200-80. single-phase (Length 80cm)
CP-FLEX 10k/1k-120. single-phase (Length 120cm)

Programs
ENERGY: Basic program that permits to measure voltages, currents, powers and energies from any phase and to save in memory the results over regularly recording periods.

HARMONIC (OPTIONAL): The program for harmonic measurement includes all the functions that the standard program offers, but also these functions related to the harmonic measurement according to the harmonized standards IEC 61000-4-7.

FLICKER (OPTIONAL): The program for Flicker measurement includes all the functions that the standard program offers, but also these functions related to the measurement of voltage fluctuations, so delivering Pst and Plt, values required according to the harmonized Standard IEC- 61.000-4-15.

DISTURBANCES (OPTIONAL): The program for disturbances measurement program permits to detect and record short or longtime voltage changes in form of spikes, dips, short-interruptions, sags, ... in dependence on preset limits.

FAST CHECK (OPTIONAL): This program has been designed for to make easy the capture of the short duration transients (starting motors and so on) obtaining registers of all of the cycles or averages from some of them.

CHECK METER (OPTIONAL): This program is specially designed to permit checking actions over energy counters, either for active or reactive energy.