TEST VOLTAGES 500 V - 1 kV -
2.5 kV - 5 kV directly, one button selectable. 500 V
to 5 kV in 25 V, 100 V or 500 V
steps. DC, negative.
MAXIMUM RESISTANCE
READING 5 TΩ @ 5 kV
DC VOLTMETER 30 V
up to 600 Vdc Accuracy: ±(5 % of reading + 3 digits)
AC
VOLTMETER 30 V up to 600 V r.m.s. Accuracy:
±(5 % of reading + 3 digits)
OVERVOLTAGE CATEGORY CAT.
III - 600 V
LEAKAGE CURRENT MEASUREMENT 1 nA
up to 1500 nA ±(10 % of reading + 3 digits)
CAPACITANCE
MEASUREMENT 50 nF up to 10 µF
@ 500 V 50 nF
up to 5 µF @
1000 V 30 nF up
to 2 µF @ 2500 V 30 nF
up to 1 µF @
5000 V Accuracy:
±10 % of reading ± 3 digits
SHORT CIRCUIT CURRENT Max.
2 mA
TEST VOLTAGES ACCURACY ± 3 % of
nominal test voltages on 10 GΩ
MEGOHMMETER
BASIC ACCURACY ± 5 % of reading 1 MΩ to 1 TΩ @ 5 kV ±
20 % of reading 1 TΩ to 5 TΩ @ 5 kV (for lower test voltages,
the upper limit will be reduced proportionally) ±
20 % of reading 10 kΩ to 100 kΩ ± 10 % of reading 100 kΩ
to 1 MΩ
ADVANCED FEATURES Automated
Polarization Index calculation Automated Dielectric
Absorption Ratio calculation Programmable Pass-Fail
test Step Voltage Test 4000 readings memory Switchable
filter to remove external noise interference
BUILT-IN
PRINTER Prints elapsed time, actual voltage and
resistance measured each 15 seconds
SERIAL
DATA OUTPUT RS-232 @ 4800 bps. With optical isolation.
Suitable for data collection in an external serial printer,
computer or data-logger.
|
BUILT-IN CHRONOMETER Shows elapsed time
in mm:ss format. Count starts automatically for each
measurement.
MEGALOGG2 SOFTWARE Friendly,
easy to use software. Tests are represented in graphic
and tabular views. With automatic report generator,
including the operator's commentaries.
ENVIRONMENTAL
PROTECTION IP-54 (with closed lid)
SAFETY
CLASS Meets the requirements of IEC 61010-1/1990,
IEC 61010 1/1992 amendment 2
E.M.C In
accordance with IEC 61326-1
ELECTRO MAGNETIC
IRRADIATION IMMUNITY In accordance with IEC 61000-4-3
ELECTROSTATIC
IMMUNITY In accordance with IEC 1000-4-2
POWER
SUPPLY Internal rechargeable 12 V - 3 Ah NiMH
battery
BATTERY CHARGER For 100 - 240 V~
mains
OPERATING TEMPERATURE RANGE -5 ºC
to 50 ºC
STORAGE TEMPERATURE RANGE -25 ºC
to 65 ºC
HUMIDITY RANGE 95% RH (non
condensing)
ALTITUDE Up to 3000 m
WEIGHT Approx.
4.3 kg
DIMENSIONS 340 x 295 x 152 mm
INCLUDED
ACCESSORIES: • 2x Measuring test leads (25 kV
insulation) • 1x GUARD test lead • Charger power
cord • RS-232 cable • Protective bag • Operating
instructions • MegaLogg2 software • 10 printer
paper rolls
|