:: home > megohmmeters > high voltage > max. voltage 15 kV
MI-15KVe - TECHNICAL SPECIFICATIONS

Test voltages (T.V.)
1 kV - 5 kV - 10 kV - 15 kV

Maximum resistance reading
200 GΩ @ 1 kV (T.V.)
1 TΩ @ 5 kV (T.V.)
2 TΩ @ 10 kV (T.V.)
3 TΩ @ 15 kV (T.V.)


Short circuit current
1 mA

Test voltages accuracy
± 2% of nominal test voltages on R
³ 10 GΩ

Megohmmeter accuracy
class 2 (± 2% of full scale deflection)

Internal current limiting resistance
1 MΩ @ 1 kV (T.V.)
5 MΩ @ 5 kV (T.V.)
10 MΩ @ 10 kV (T.V.)
15 MΩ @ 15 kV (T.V.)

Analogue indicator
up to 98 mm scale length, taut band, with mirror

Environmental protection
IP54 with closed lid.

Safety class
In accordance with IEC 61010-1

Electrostatic immunity
In accordance with IEC 61000-4-2

Electro magnetic irradiation immunity
In accordance with IEC 61000-4-3

I11012811

Power supply
Internal rechargeable 12 V - 7 Ah sealed lead acid battery

Battery charger
For 110-127 or 220 V~ mains supply

Operating temperature range
-5°C to 50°C

Storage temperature range
-25°C to 65°C

Humidity range
95% RH (non condensing)

Altitude maximum
2000m

Weight
Approx. 9,7 kg

Dimensions
378 x 308 x 175mm

Included accessories
• Measuring test leads, 1,80 m. (2)
• GUARD test lead, 1,80 m.
• Protective case.
• Charger power cord.
• Operating instructions


CE mark

 I04032401