:: home > micro-ohmmeters > high current > max. current 100 A
MPK-102 - TECHNICAL SPECIFICATIONS

Test currents
1 mA, 10 mA, 100 mA, 1 A, 10 A, 100 A
Each current may be continuously adjustable from 0 to 100%

Measurement ranges

I nominal

Range

Resolution

100 A

0-199.9 µΩ

0,1 µΩ

100 A

0-1999 µΩ

0,1 µΩ

10 A

0-1999 µΩ

1 µΩ

10 A

0-19.999 mΩ

1 µΩ

1 A

 0-19.99 mΩ

 10 µΩ

1 A

 0-199.99 mΩ

 10 µΩ

100 mA

 0-199.9 mΩ

 100 µΩ

100 mA

 0-1999.9 mΩ

 100 µΩ

10 mA

0-1999 mΩ

 1 mΩ

10 mA

0-19.999 Ω

 1 mΩ

1 mA

0-19.99 Ω

 10 mΩ

1 mA

0-199.99 Ω

 10 mΩ

For each test current, ranges are automatically selected for optimal reading.

Output voltage
Up to 10 Vd.c. (open circuit) @ 1 A. getting a fast stabilization in the measurement of great transformers.

Measurement principle
Four-terminal, Kelvin-type.

Continuous operation time
At 100 A this equipment may be used continuously for aprox. 15 minutes before the thermal protection activates. At 10 A or less, there is not a limited time for continuous operation.

Protections
The micro-ohmmeter has protections of fast action and by overheating that protects all the sensitive components.

Basic accuracy
± 0,20 % of reading ± 0,05 % of range.

Advanced features
Digital direct reading of very low resistances in the alphanumerical display, with up to 4½ digits. Very fast and accurate measurements.

Test current measurement
Although the current is digitally measured, an analogue taut band instrument show the result  in order to facilitate the evaluation. This is specially useful when measuring inductive loads, so that the operator can verify easily when the test current has been stabilized

Serial data output
RS-232 @ 4800 bps. Suitable for data collection in an external serial printer, computer or data-logger.

Environmental protection
IP54 with closed lid.

Safety class
Meets the requirements of IEC 61010-1/1990, IEC 61010  1/1992 amendment 2

Power supply
Mains or internal battery powered
Battery is rechargeable, sealed lead-acid, 12 V 7 Ah
Mains: 110-127 or 220-230 V~
Internal battery is useful for up to 10 A .
Mains power is useful for any test current, including 100 A

Built-in battery charger
For 110-127 or 220 V~ mains

Operating temperature range
-5°C to 50°C

Storage temperature range
-25°C to 65°C

Humidity range
95% RH (non condensing)

Altitude maximum
3000m

Weight
Approx. 13,9 kg.

Dimensions
502 x 394 x 190mm

Included accessories
Combined current and potential leads for 100 A (2)
Combined current and potential leads for 10 A (2)
Aluminum case for the accessories
Power cord.
Operating instructions