APPLICATION Earth resistance measuring
of simple or complex electrode systems, Ground resistivity
measurements (Four terminal Wenner´s principle), and
Spurious voltage according to IEC 61557-5
RESISTANCE
MEASUREMENT METHOD The equipment injects an electronically
generated current in the soil, and measures, with high
precision, both that current and the voltage developed
in the soil by means of that current flowing through
grounding diffusion resistance. The display shows the
Resistance value.
OPERATION FREQUENCY During
R measurement operators should select the following
test frequencies: 270 Hz ± 1 Hz or 1470 Hz ± 1 Hz
VOLTMETER In
the voltmeter function, the equipment operates as a
CA conventional voltmeter, making it possible to measure
voltages generated by parasitic currents.
MEASUREMENT
RANGES Resistance: 0 - 20kΩ (autoranging) Resistivity:
0 - 50kΩm (autoranging) Voltage: 0 - 60V~
ACCURACY Resistance
and Resistivity measurements: ± (2% of the measured
value ± 2 digits) Voltage measurement: ± (3% of the
measured value ± 2 digits)
READING RESOLUTION 0.01Ω
in the resistance measurement. 0.01Ωm in the
resistivity measurement. 0.1V in the voltage measurement.
OUTPUT
CURRENT The short-circuit current is limited
to less than 3.5mA r.m.s. (according the IEC 61557-5
- 4.5 )
IMMUNITY TO SPURIOUS VOLTAGE
INTERFERENCE During the R measurement, it allows
for the presence of spurious voltage up to 7V~.
EARTH
RESISTANCE OF AUXILIARY RODS In the R measurement
it allows Raux up to 50kΩ with error <
30%
BATTERY STATUS CHECKING The battery
charge status is verified under normal using conditions.
ADVANCED
FEATURES Automated detection of abnormal conditions
that may cause excessive errors (low battery, too high
noise interference, too high test spikes resistance)
SOIL
RESISTIVITY COMPUTING When performing soil resistivity
measurements, the operator informs to the EM-4055 the
distance between spikes and the equipment automatically
computes soil resistivity using the Wenner full equation.
|
SERIAL DATA OUTPUT RS-232 @ 4800 bps. Suitable
for data collection in an external serial printer, computer
or data-logger.
BUILT-IN PRINTER (OPTIONAL) For
a printed register document of measured values.
POWER
SUPPLY By means of an internal rechargeable battery,
12V 2.3Ah.
BATTERY CHARGER A smart, microprocessor-controlled, circuit that adjusts the battery charge to the optimised parameters in order to ensure highest service life. For 100-240 V mains supply.
SAFETY CLASS It
meets the requirements of IEC 61010-1/1990, IEC 61010,
1/1992 amendment 2
E.M.C In accordance
with IEC 61326-1
ELECTROSTATIC IMMUNITY In
accordance with IEC 1000-4-2
ELECTRO MAGNETIC
IRRADIATION IMMUNITY In accordance with IEC 61000-4-3
ENVIRONMENTAL
PROTECTION IP54 with closed lid.
OPERATION TEMPERATURE -10°C
to 50°C
STORAGE TEMPERATURE -25°C to
65°C
HUMIDITY 95% RH (without condensation)
EQUIPMENT
WEIGHT Approximately 3.6kg (without printer)
SIZE 274
X 250 X 124 mm
INCLUDED ACCESSORIES Four steel rods. One charger power cord.
One 40 meters cable in
red colour. Two 20 meters cable in blue and green
colour. One 5 meters cable in black colour. One 5 meters cable to connect to the grounding system
to be measured. One canvas bag.
|