MEASUREMENT RANGES 0 - 300 Ω
OPERATION FREQUENCY 25,000 Hz
TEST CURRENT 20 mA automatic
INDUCTIVE COMPONENT COMPENSATION Through bank of capacitors integrated to the equipment Maximum capacity: 4.2 µF Resolution: 10 nF
MEASUREMENT ACCURACY ± 2.5 % of reading ± 1 digit
DISPLAY Alphanumeric display (LCD)
MAX. EARTH RESISTANCE OF AUXILIARY RODS 2,000 Ω (current rod) 2,000 Ω (voltage rod)
BUILT-IN MEMORY It allows for the storage of 2,000 tests readings in its internal NVRAM memory.
SERIAL DATA OUTPUT RS232 @ 4800 bps.
POWER SUPPLY Internal or external rechargeable battery, 12 V. Internal battery autonomy: at least 2 hours
BATTERY CHARGER For 100 - 240 V~ 50/60 Hz
|
OPERATING TEMPERATURE -5°C to 50°C
STORAGE TEMPERATURE -15 °C to 65 °C
HUMIDITY Up to 95% RH (non condensing)
ACCESSORIES 4x 50 cm long steel core rods with copper coating 1x Rod extractor 1x 70 m shielded cable 1x 50 m shielded cable 1x 30 m cable to current rod 1x 70 m cable to auxiliary potential rod 1x 50 m cable to auxiliary potential rod 1x Cable adapter for current electrode 1x External battery cable 1x Cable for connection to the unknown electrode (Tower) 1x Case to carry accessories 1x Operating handbook
DIMENSIONS 340 x 295 x 152 mm
EQUIPMENT WEIGHT Approx. 4.5 kg
|